DATASHEET
SkelMod 162V62F

- 162V DC nominal voltage
- Ultra-low ESR
- Long lifetime - 1 million duty cycles
- High power outpu
| Electrical | Value | Unit |
|---|---|---|
| Nominal voltage | 162 | V |
| Absolute maximum voltage | 170 | V |
| Rated capacitance | 62 | F |
| Rated DC 10ms ESR | 10.9 | mOhm |
| Rated DC 1s ESR | 13.0 | mOhm |
| Rated maximum peak current (for 1 s duration)1,9 | 2.78 | kA |
| Typical short circuit current (For informational purposes - do not use as operating current.) | 14.9 | kA |
| Maximum stored energy2 | 225 | Wh |
| Cells in total | 54 | pcs |
| Cell configuration | 54s1p |
| Physical parameters | Value | Unit |
|---|---|---|
| Mass. Typical | 35.0 | kg |
| Dimensions (LxWxH) Width indicates the dimensions for the front panel, the rest of the module is narrower and usable in a 19” rack. | 540 x 483 x 172 | mm |
| Temperature | Value | Unit |
|---|---|---|
| Operating temperature range* | ||
| Operating temperature range*, Minimum | -40 | °C |
| Operating temperature range*, Maximum | +60 | °C |
| Storage temperature range (uncharged) | ||
| Storage temperature range (uncharged), Minimum | -40 | °C |
| Storage temperature range (uncharged), Maximum | +50 | °C |
| Life | Value | Unit |
|---|---|---|
| Lifetime @ 162V and maximum operating temperature | 1500 | Hours |
| Storage life @ RT, uncharged | 10 | Years |
| Projected cycle life @ RT, between VR and VR / 2 | 1,000,000 | Cycles |
| Power | Value | Unit |
|---|---|---|
| Rated nominal power, calculated from 10 ms ESR | ||
| Power6 | 601 | kW |
| Rated practical power, calculated from 1 s ESR | ||
| Power6 | 504 | kW |


Notes
* For maximum series voltage IE32 (EN 60721-3-3) requirements must be followed. For lower temperature contact Skeleton Technologies
** Inrush current for the auxiliary supply: 0.18A
*** Thermal parameters given for cooling airflow rate of 85CFM
(9) The stated maximum peak current should not be exceeded during use. If the limit is to be exceeded by the customer, Skeleton must be consulted beforehand and give approval for the exceeded power load. (10) These values of current refer to begin of life conditions of the
product, for system design 200% ESR should be considered.
Standard Markings
+ Name of manufacturer, part number, serial number, rated voltage
+ Rated capacitance, negative and positive terminals, warning marking
+ Total energy in watt-hours
Notes
+ All information provided on this data sheet and all subsequent supercapacitors sales and testing are subject to Standard Terms of Service (ToS) available on www.skeletontech.com, document General Terms of Sale for Skeleton Technologies GmbH